Page image not rendered yet. The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text
OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
AIRBORNE ASBESTOS ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY
CLIENT: Warren & Panzer Engineers, P.C. PROJECT: NYC DEP, 50 Broadway, Manhattan, New York
ATUPNir A laboratory ID #: T02 08 102 DATE OF REPORT: 08/20/02
A I nt IM IGA aNALYT. METHODOLOGY: AHERA DATE OF ANALYSIS: 08/20/02
ENVIRONMENTAL SERVICES INC. pyLTgR TYPE: M C E.
EFFECTIVE FILTER AREA (mm^): 385
I*
rBX. (718/ /84—^(W5
AVERAGE G.O. AREA (mm’): 0 012422
LABORATORY RESULTS
CLIENT LAB. ID LOCATION YOLUME G.O.’s AREA ANALYT. TOTAL TOTAL AIR AIR ASBEST. AMPHIB.
# # (It) ANAL ANALY SENSITIV. ASBESTOS ASBESTOS CONC. CONC. TYPE ASBEST
YZED ZED (struct./cni’) AIR CONC. FILTER FOR FOR CHRYS. TYPE
(mm^) (struc./cm’) CONC. STRUCT. STRUCT. SPECIFY
(str./inm’) 0.5<S<5nin S25.0nin
01 T02-08- At North east 1800 4 0.0497 0.0043 <0.0043 <20.13 NA NA NA NA
102-1727 comer on 17*
floor
02 T02-08- At entrance to 1800 4 0.0497 0.0043 <0.0043 <20.13 NA NA NA NA
102-1728 North east comer
on 17* floor
03 T02-08- At South east 1800 4 0.0497 0.0043 <0.0043 <20.13 NA NA NA NA
102-1729 comer on 17*
floor
04 T02-08- At North west 1800 4 0.0497 0.0043 <0.0043 <20.13 NA NA NA NA
102-1730 comer on 17*
floor
05 T02-08- At South west 1800 4 0.0497 0.0043 <0.0043 <20.13 NA NA NA NA
102-1731 comer on 17*
floor
ANALYST LABORATORY DIRECTOR
o E. Sioukri Spiro Dongaris
H
K LABORATORY CERTIFICATION NUMBERS: NVLAP 101958, ELAP 10955
I
to
Athenica Environmental Services Inc (AES), is responsible only for information pertaining to samples taken by its employees.
Air sampling cassettes will be stored for sixty (60) days. AES Inc., should be notified within this time frame for a true duplicate analysis.
o If AES Inc., did not conduct the sampling, the reported airborne concentration was derived based on information provided by the client. Under these circumstances, the air concentration data is
o supplied solely for the convenience of the clienl.
Io
I'he report relates only to items tested This report must not be used to claim product endorsement by NVI AP or any other agency of the U.S. Government. Test reports may not be reproduced
o except in full and with prior approval of AliS Inc.
co
The liability of Athenica Environmental Services Inc with respect Io the services charged, shall in no event exceed the amount of the invoice