NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Memo: Indoor air quality report, PS 89M, Jun 2002

Machine-extracted title · confidence 32%

ATC report of indoor air quality (lAQ) for P.S. 89M, 201 Warren Street.

NYC-WTC_000340473–000340476
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

®005/014 06/14/2002 13:35 FAX 212 353 8306 ATC

Mr. Bernard P. Orlan June 14, 2002 Indoor Air Quality Assessment Page 4 P. S. S9M ATC Project No. 15-19125-0297 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVQC Concentratioiis

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVQC concentration was also 0.0 ppm.

OBSOVAnWS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in Ure building • The interior of the building appear ed clean and free of dust and debris.

FmPlNGS Based on the real-time measurements, the following findings are presented: I. Concentrations of CO, CO2 and TVOCs were below applicable standards and guidelines. 2. Eleven (11) of the indoor measurements for temperature were below tire range of 73 to 79'’F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recomraended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements for PM2.5 were above tire NPAAQS of 65 ug/m.^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children,

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, ext 211 or 212.

Sincerely, Reviewed by: ATCASSOCIATES INC

L/ Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_009261477 NYC-WTC_000340476

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340476Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →