Memo: Indoor air quality report, PS 89M, Jun 2002

Machine-extracted title · confidence 32%

ATC report to BOE on indoor air quality at P.S. 89M, Warren Street, Jun 2002.

NYC-WTC_000340437–000340440
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

i 06/24/2002 11:03 FAX 212 353 8306 ATC @002/014

104 East 25th St. lOth Floor New Vork. New York 10010 WWW. ate- envi ro, com 212.353.8280 Fax 212,353,8306 ASSOCIATES INC.

June 24, 2002

Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101 -4008

Re; Indoor Air Quality Assessment P.S. 89M 201 Warren Street New York, New York 10282 ATC Project No. 15-19125-0297

Dear Mr. Oilau;

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on Jtuie 21, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements to evaluate air quality in tire school building.

SC^EOFWORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO,) and carbon monoxide (CO).

ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.

ATC measured concentrations of respirable particulates (PMj s) with a Dust-Trak® Aerosol Monitor Model S520, manufactured by TSI, Inc.

ATC measmed concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE Systems, Inc. MiniRAE® photoionization detector (PID),

J Mr. Kevin Fitzpatrick, Environmental Technician, of ATC’s New York City office, conducted the assessment.

ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in die school at the time of the assessment.

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on tlic dates of tlie survey and may not represent conditions found at otlicr times. The information

CITY_21MC100_012158176 NYC-WTC_000340437

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340437Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →