NYSDOL - DOSH Regulations - Reg Page 24 of 44 time and the integrity of wall barriers, for secure attachment or the need for additional reinforcement, shall be checked. Units connected in series shall be considered a single unit for this test. A minimum of one additional unit, having a capacity at least equal to that of the primary unit, shall be installed as a backup to be used during primary unit filter changing and upon primary unit failure.

(e) Power supply. A power supply shall be available to satisfy the requirements of the total of all ventilating units.

(f) Power failure.On electric power failure, abatement shall stop immediately and shall not resume until power is restored and exhaust units are operating fully. On extended power failure, longer than one hour, the decontamination facilities, after the evacuation of all persons from the work area, shall be sealed airtight.

(g) Air changes.Negative pressure ventilation equipment shall be installed and operated to provide at least four air changes in the work area every hour.

(h) Openings in enclosure.Openings made in the enclosure system to accommodate these units shall be made airtight with tape and/or caulking. Where possible, only the intake and the filter access panel shall remain within the work area to permit filter changing, while minimizing equipment contamination and the likelihood of contamination of nonwork areas.

(i) Installation and care.Negative pressure ventilation units shall be exhausted to the outside of the building or structure and away from occupied areas. Proper installation, air monitoring and daily inspections shall be conducted to insure that the ducts do not release asbestos into uncontaminated areas. Fans, ducts and joints shall comply with the following:

(1) Ducts, of at least equivalent shape and dimension as that of the negative pressure ventilation exhaust, shall be used to exhaust to the outside of the building or structure.

(2) Airtight system. All fans, ducts and joints shall be sealed, braced and supported to maintain an airtight system.

(j) Exhaust location. At no time shall the negative pressure ventilation unit exhaust within 50 feet of a receptor or adversely affect the air intake of the building/’structure or other buildings/structures.

Historical Note: Sec. filed July 7, 1987; amd. filed Oct. 18, 1991 eff. Jan. 1, 1992. Amended (c),(i)(l). Subpart 56-7. MATERIALS AND EQUIPMENT

Historical Note: Subpart (§56-7.1) filed July 7, 1987 eff. July 28, 1987. § 56-7.1 General requirements.

(a) Storage of materials.Materials shall be stored off the ground, away from wet or damp surfaces and under protective cover to prevent damage or contamination. Replacement materials shall be stored outside the work area and enclosure until abatement is completed.

(b) Damaged or deteriorating materials.Damaged or deteriorating materials shall not be used and shall be removed from the premises.

(c) Fireproofing or insulation protection. When asbestos material that has been used for fireproofing or insulation protection has been removed, protection, at least equivalent to that removed, shall be provided and installed in conformance with all applicable codes.

(d) Plastic sheeting.Fire-retardant plastic sheeting of at least six-mil thickness, in sizes and shapes to minimize

http://www.labor.state.ny.us/html/safety/s56.htm 01/20/2001

CITY_21MC100_012156416

NYC-WTC_000340391

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000340391Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000446470

State Part 56 asbestos chain-of-custody/document referencing NY Department of Labor; NYC files.

Similar indexed content

Compare copies and versions →