NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Stuyvesant High School, Mar 2002

Machine-extracted title · confidence 40%

Indoor air quality measurements documented for Stuyvesant HS.

NYC-WTC_000336438–000336441
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 15, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 10-20 pg/m^ with an average of approximately 17 pgnA.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration TVOCs inside the building were 0.0 ppm to 0.1 ppm The outdoor TVOC concentrations were 0.0 ppm to 0.2 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO ,CO2, and TVOCs, were within applicable standards and guidelines. 2. Nine (9) measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. Three (3) temperature measurements were below and one (1) was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. None of the indoor particulate measurements were above the NPAAQS of 65pg/m3 or above the USEPA recommendation of 40pg/for sensitive individuals and children. Both outdoor readings were above the USEPA recommendation of 40pg/m3 for sensitive individuals and children. It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212. Sincerely, J TC ASSOCL4 T£S INC. Reviewed by:

Yiannis Efstathiou James R. Cohn, CIH/CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO3O61459 NYC-WTC_000336441

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336441Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000269995

March 8, 2002 memo regarding IAQ sampling at Stuyvesant High School (M477).

Similar indexed content

NYC-WTC_000402156

ATC IAQ measurements report for Stuyvesant High School dated March 2002.

Similar indexed content

Compare copies and versions →