Mr. Bernard P. Orlan May 8, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 15-26 pg/m^ with an average of approximately 22 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented: 1. Concentrations of CO , CO2 and TVOCs were below applicable standards and guidelines. 2. Sixteen (16) measurements of relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. One hundred and ten (110) temperature measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). 4. All indoor respirable particulate measurements were below the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212. Sincerely, H TC ASSOCIA TES INC.

Reviewed by: I

( /Yiannis Efstathibu James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_002902991

NYC-WTC_000406698

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406698Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000229527

Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 8, 2002.

Similar indexed content

Compare copies and versions →