Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected April 17, 2002 at Stuyvesant High School.
NYC-WTC_000336220–000336223OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 18, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 for these rooms concentration ranged from 33 -52 pg/m^ with an average of approximately 44 Pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration TVOCs inside the building wereO.O ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented: 1. Concentrations of CO2, CO , and TVOCs, were below applicable standards and guidelines. 2. Forty (40) of the measurements were below and one (1) measurement was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. One (1) measurement was above and one hundred-seventeen (117) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 4. Five (5) of the indoor measurements for PYb j were above the NPAAQS of 65 pg/m3 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Forty-nine (49) of the one hundred seventeen (117) instantaneous readings were above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education, If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.
Sincerely, /I TC ASSOCIA TES INC.
Reviewed by: < \ —
Amel Javaby James R. Conn Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC1OO_OO3O61115 NYC-WTC_000336223
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336268
ATC reports IAQ measurements collected at Stuyvesant High School on Apr 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229470
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406544
April 12, 2002 memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406560
April 15, 2002 memo referencing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336273
ATC IAQ report for Stuyvesant High School dated Apr 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336182
Indoor air quality measurements at Stuyvesant High School documented April 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406646
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406600
April 22, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372722
Indoor air quality measurements at Stuyvesant High School conducted April 18, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336237
IAQ measurements collected April 19, 2002 at Stuyvesant High School.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336438
Indoor air quality measurements documented for Stuyvesant HS.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000270026
ATC IAQ measurements conducted March 15, 2002 at Stuyvesant High School for NYC BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402206
ATC IAQ measurements report for Stuyvesant High School, March 15, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
Similar indexed content
NYC-WTC_000336268
ATC reports IAQ measurements collected at Stuyvesant High School on Apr 24, 2002.
Similar indexed content
NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
Similar indexed content
NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
Similar indexed content