Mr. Bernard P. Orlan May 3, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477)______________ ATC Project No. 15-19125-0246 Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:25 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.4°F to 73.6°F. One hundred and fifteen (115) of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature range was 54.2 to 57.4°F.
Relative Humidity
The relative humidity indoors ranged from 41.4 percent to 61.7 percent. Five (5) of the measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 65.8 and 86.8 percent.
Carbon Dioxide Concentrqtim
Carbon dioxide concentrations indoors ranged from 455 ppm to 1196 ppm. Thirteen (13) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 389 and 426 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1126 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 11 pg/m^ to 21 pg/m^ with an average of approximately 15 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 ugAn' for sensitive individuals and children. The outdoor respirable particulate concentrations were 34 and 36 pg/m^.
ClTY_21MC100__003060615
NYC-WTC_000336062
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229470
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336273
ATC IAQ report for Stuyvesant High School dated Apr 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406560
April 15, 2002 memo referencing IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406695
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372924
ATC delivers IAQ report for Stuyvesant High School (M477) dated May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406646
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000336065
IAQ measurements collected May 3, 2002 for Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336093
May 2002 IAQ measurements at Stuyvesant High School, BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406670
ATC field report documenting IAQ measurements at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406642
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336273
ATC IAQ report for Stuyvesant High School dated Apr 25, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406666
Indoor air quality measurements at Stuyvesant High School, May 2002, for DOE.
Similar indexed content
NYC-WTC_000336056
IAQ measurements collected May 1, 2002 for Stuyvesant High School; BOE request.
Similar indexed content
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 16, 2002.
Similar indexed content
NYC-WTC_000372779
Indoor air quality measurements collected at Stuyvesant High School, April 24, 2002.
Similar indexed content
NYC-WTC_000406675
Indoor air quality measurements at Stuyvesant High School, May 2002, by ATC Associates for DOE.
Similar indexed content