Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗IAQ measurements collected April 30–May 2, 2002 for Stuyvesant High School.
NYC-WTC_000336051–000336054OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
(Skk 104 East 25th St., 10th Floor New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8.306 ' A SSOCIATES INC.
May 1, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on April 30, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO2) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Herant Antonyan, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclu.sions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used
CITY_21MC1OO_OO3O6O577 NYC-WTC_000336051
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406650
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406544
April 12, 2002 memo detailing IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336093
May 2002 IAQ measurements at Stuyvesant High School, BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406712
IAQ measurements collected on May 9, 2002 at Stuyvesant High School for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372796
Indoor air quality measurements collected May 1, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406642
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336237
IAQ measurements collected April 19, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336289
ATC IAQ report for Stuyvesant High School; March 4, 2002 entry.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336098
May 13–14, 2002 IAQ measurements at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372830
Indoor air quality report for Stuyvesant High School dated May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000407007
ATC IAQ report to NYC Board of Education for Stuyvesant High School, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274071
IAQ measurements report for Stuyvesant High School, June 2002, sent to NYC Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335934
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407030
ATC IAQ report for Stuyvesant High School dated June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406650
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
Similar indexed content
NYC-WTC_000406544
April 12, 2002 memo detailing IAQ measurements at Stuyvesant High School.
Similar indexed content
NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similar indexed content
May 2002 IAQ measurements at Stuyvesant High School, BOE request.
Similar indexed content
NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
Similar indexed content