NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗IAQ measurements collected June 25, 2002 at Stuyvesant High School for BOE.
NYC-WTC_000336024–000336028OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Measurements Page 4 Stuyvesant High School (M477)ATC Project No. 15-19125-0246 concentration range for these rooms was 24 - 32 ug/m- with an average of approximately 28 pg/ni3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs inside the building were 0.0 ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The barge operation at Pier 25 has been shut down.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines. 2. Forty-seven (47) of the indoor temperature measurements were below and one (1) was above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the mechanical cooling season (summertime conditions). 3. One (1) of the indoor measurements for relative humidity was above the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. 5. All of the indoor CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level.
CITY_21MC100_003060523
NYC-WTC_000336027
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373066
ATC IAQ measurements collected on June 4, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373210
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204420
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406985
Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204425
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406932
IAQ measurements at Stuyvesant High School for NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407013
ATC report of IAQ measurements conducted June 20, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335934
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373179
ATC report of indoor air quality measurements at Stuyvesant High School from June 13, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000204420
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335934
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373210
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373066
ATC IAQ measurements collected on June 4, 2002 at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406915
ATC IAQ report for Stuyvesant High School issued June 2002 to NYC Board of Education.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
Similar indexed content
NYC-WTC_000373066
ATC IAQ measurements collected on June 4, 2002 at Stuyvesant High School.
Similar indexed content
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
Similar indexed content
NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
Similar indexed content
NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similar indexed content