Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at Stuyvesant High School, June 2002.
NYC-WTC_000406985–000406989OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
104 East 25th St., 10th Floor New York. New York 10010 wwwatc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.
June 18, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on June 17, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO,) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Herant Antonyan, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_003797768
NYC-WTC_000406985
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335934
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373210
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406975
ATC IAQ report issued to NYC Board of Education for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373264
Letter/report detailing indoor air quality measurements at Stuyvesant High School on June 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204425
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406932
IAQ measurements at Stuyvesant High School for NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373066
ATC IAQ measurements collected on June 4, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406947
Report of indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407047
Report of IAQ measurements collected June 24, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000373004
ATC IAQ measurements collected on May 29, 2002 at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372826
Indoor air quality measurements collected May 1, 2002 at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406906
Indoor air quality measurements at Stuyvesant High School documented for NYC Board of Education, May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406626
April 26, 2002 memo referencing IAQ measurements at Stuyvesant High School.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000213072
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 16, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373084
ATC report detailing indoor air quality measurements at Stuyvesant High School during June 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similar indexed content
NYC-WTC_000335962
Station measurements at Stuyvesant High School IAQ requested by NYC BOE, June 2002.
Similar indexed content
NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
Similar indexed content
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similar indexed content
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
Similar indexed content