Mr. Bernard P. Orlan June 14, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477) ATC P rpiect No. 15-19125-0246 The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER TARGETLEVEL AGENCY OR ■* ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 qg/m- 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003060388
NYC-WTC_000335963
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406985
Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373210
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406975
ATC IAQ report issued to NYC Board of Education for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204425
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335934
Indoor air quality measurements report for Stuyvesant HS, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336024
IAQ measurements collected June 25, 2002 at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406932
IAQ measurements at Stuyvesant High School for NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373066
ATC IAQ measurements collected on June 4, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407047
Report of IAQ measurements collected June 24, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407013
ATC report of IAQ measurements conducted June 20, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406622
April 25, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406970
Indoor air quality measurements at Stuyvesant High School prepared for Board of Education, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335929
Indoor air quality measurements report for Stuyvesant HS, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336098
May 13–14, 2002 IAQ measurements at Stuyvesant High School for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406646
Indoor air quality measurements at Stuyvesant High School, April 2002, by ATC Associates for DOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204425
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406985
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similar indexed content
NYC-WTC_000406990
Indoor air quality measurements at Stuyvesant High School, June 2002.
Similar indexed content
NYC-WTC_000335984
IAQ measurements collected for Stuyvesant High School; BOE requested thes[e] results.
Similar indexed content
ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.
Similar indexed content
NYC-WTC_000406975
ATC IAQ report issued to NYC Board of Education for Stuyvesant High School, June 2002.
Similar indexed content