NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, High School for Leadership & [name], Feb 2002

Machine-extracted title · confidence 45%

Indoor air quality measurements collected at the referenced school under BOE request.

NYC-WTC_000335530–000335533
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 27, 2002 Indoor Air Quality Assessment Page 3 U.S. for Leadershin & Pub. Sendee (M894') ATC Project No. 15-19125-0290

Real-Time Ena ironmental Measurements

ATC collected one: hundred and sixty (160) sets of real-time environmental measurements consisting of one hundred and fifty-eight (158) in the school building and two (2) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:27 A.M. and concluded after 1:43 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 62.6°F to 76.3°F. Two (2) of the measurements were: above and three (3) were below the range of 68 to 75°F (at 50 percent relative humidify) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 59.8°F to 65.5°F.

Relative Humidity

The relative humidity indoors ranged from 32.3 percent to 43.4 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 35.3 to 39.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 443 ppm to 1497 ppm. Six (6) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged from 398 ppm to 480 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1180 ppm (background level + 700 ppm). The highest reading was recorded in Room 1403 at around 8:30 A.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The: primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 -3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2-8 ppm.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 48 pg/m^ with an average 22 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 67 pg/m^ to 90 pg/m^ ,

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_003059047

NYC-WTC_000335532

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335532Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335550

Indoor air quality measurements collected at the referenced school.

Similar indexed content

NYC-WTC_000335512

Indoor air quality measurements performed at the referenced high school per BOE request.

Similar indexed content

Compare copies and versions →