Indoor air quality report, High School for Leadership, Feb 2002

Machine-extracted title · confidence 40%

ATC IAQ measurements collected February 15, 2002 at the referenced school.

NYC-WTC_000335452–000335455
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Oilan February 18, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Pub. Service (M894) ATC Project No. 15-19125-0290

TVOC Concentration

lY^OCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • Tire interior of the building appeared clean and free of dust and debris; • The building v/as occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of respirable particulates, CO , CO2 and TVOCs, were within applicable standards and guidelines. 2. Six (6) temperature measurements were below and fifteen (15) were above the range of 68 to 75°F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the heating season ('wintertime conditions). 3. One hundred and thirty-two (132) of the relative humidity measurements w-ere below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The other two (2) measurements were within the recommended range.

■It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, ATC ASSOCIA TES INC. Reviewed by:

Yiannis Efstathiou James R. Cohn, CIH, CSP Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_0 03058950

NYC-WTC_000335455

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335455Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335364

ATC IAQ measurements collected February 8, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000335402

ATC IAQ measurements collected February 12, 2002 for the referenced school.

Similar indexed content

Compare copies and versions →