NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February'13, 2002 Indoor Air Quality' Assessment Page 3 H.S. for Leadership & Pub. Service (M894) ATCProiectNo. 15-19125-0290

Real-Time Envtronmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 2:40 P.M. The results are described below.

Temperatiire

Indoor dry bulb temperature measurements ranged from 65.9°F to 75.2°F. Four (4) of the measurements were below' and one (1) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 40.4°F to 47.8°F.

Relative Humidi^

The relative humidity indoors ranged from 19.1 percent to 44.6 percent. One hundred and thirty' (130) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort, Tire outdoor relative humidity range was 21.1 to 28.4 percent.

Carbon Dioxide Concentrate

Carbon dioxide concentrations indoors ranged from 441 ppm to 1246 ppm. Four (4) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations ranged from 403 ppm to 432 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1132 ppm (background level + 700 ppm). The highest reading was recorded in Room B06, occupied by 22 people at around 2:40 P.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tire primary source of COy indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm. Tlrese concentrations were below the NPAAQS/ASHR/vE guideline of 9 ppm. The outdoor CO concentrations were 1-2 ppm.

Respirabie Particulates (PM2,p)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 21 pg/m^ with an average 5 pg/nr^- None of the measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 12 pg/m^ to 47 pg/m^ w'ith an average of 31 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_006752172

NYC-WTC_000335404

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335404Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335452

ATC IAQ measurements collected February 15, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000335364

ATC IAQ measurements collected February 8, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000335327

ATC reports IAQ measurements collected February 5–6, 2002 for NYC BOE.

Similar indexed content

Compare copies and versions →