Mr. Bernard P. Ori an March 21.2002 Indoor Air Quality Assessment Page 3 P. S, 150M ATCProiect NoM5-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40' sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. The.se results are described below.
f ield data sheets are found in Attachment 1. Readings began at 2:15 P.M. and concluded at approximately 3:30 P.M.
Temperature
Indoor dr/ bulb temperature measurements ranged from 69.9°F to 74.8°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the .ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 47.2 to 48.6T'.
Relative Humidity’
The relative humidity indoors ranged from 29.0 to 34.6 percent. Two (2) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort, lire outdoor relative humidity measurements ranged from 47.0 to 51.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 596 ppm to 810 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum ouldoor (background) CO? concentration was 457 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1157 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicale a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. Tire primary source of C’Or indoors is occupant respiration. The school building was occupied during ATC’s assessment.
CarbonMonoxideC^ncentration
C arbon monoxide concentrations were 0 ppm for the interior readings. Tliese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.
Respirab!e Particulates (PMjj)
Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 21 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMn.s concentration for the entire school building was approximately 10 pg/m^. fhe PMg.S average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 13 to 18 pg/m^ with an average of 15 pg/m^.
CITY_21MC100_002954236
NYC-WTC_000289428
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300705
ATC IAQ measurements at PS 150M before occupancy, Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374832
IAQ measurements at PS 150M for re-occupancy evaluation, May 23, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394388
April 2002 indoor air quality measurements at P.S. 89M.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289478
ATC memo detailing IAQ measurements conducted at PS 150M for BOE re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392600
ATC report detailing IAQ measurements conducted April 9, 2002 at P.S. 89M per BOE request.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274666
ATC IAQ report for P.S. 89M dated Feb 26, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289334
ATC indoor air quality report for PS 150M; measurements on Feb 4, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326728
ATC report of IAQ measurements at PS 89M, March 4, 2002, per BOE request.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289326
IAQ measurements at a school building to assess air quality before re-occupancy.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392600
ATC report detailing IAQ measurements conducted April 9, 2002 at P.S. 89M per BOE request.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
Similar indexed content
NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
Similar indexed content
NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similar indexed content
NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similar indexed content
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
Similar indexed content