Indoor air quality report, High School for Leadership, Feb 2002

Machine-extracted title · confidence 43%

ATC reports IAQ measurements collected February 5–6, 2002 for NYC BOE.

NYC-WTC_000335327–000335330
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Or'an February 6, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Pub. Service (M894) ATCProiect No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and thirty-nine (139) sets of real-time environmental measurements consisting of one hundred and thirty-three (133) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:20 P.M. The results are described below:

Temperature

Indoor dry bulb temperature measurements ranged from 63.8°F to 73.8°F. Thirty (32) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by .VSHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 1st, 5th , gth ,9th , ipth , nth , 12th , 13th ^^d 14tti floors. The outdoor temperature range was 35.1°F to 40.4°F.

Relative Humiditv

The relative humidity indoors ranged from 17.6 percent to 33.1 percent. All but three of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 17.6 and 33.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 415 ppm to 1282 ppm. Three (3) of the measurements were above the ASFIRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations ranged from 412 ppm to 511 ppm. Therefore, the maximum acceptable level of COg at this location was 1211 ppm (background level + 700 ppm). The highest reading was recorded m Room 1105, occupied by 27 people. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tfie primary source of COg indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0-2 ppm.

Respirable Particulates (PM2_s)

Respirable particulate concentrations* indoors ranged between 3 ug/m^ to 34 pg/. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average outdoor respirable particulate concentrations ranged from 34 pg/m^ to 59 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPA.AQS is a 24-hour average.

CITY_21MC100_006752152

NYC-WTC_000335329

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335329Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000335364

ATC IAQ measurements collected February 8, 2002 for the referenced school.

Similar indexed content

Compare copies and versions →