Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Page 3 H^forI^adtehig&PublicSentice2M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. .Ml fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb ,;em]3erature measurements ranged from 76.2 to 82.3 °F. Twenty-four (24) of the indoor measurements were above the range of 73 to79 °F (at 50 percent relative humidity) recommended by .ASHRAF Standard 55-1992 during the summer season. The outdoor temperature ranged from 84.1 to 89.1 °F.

Relative Humidity

The relative humidity indoors ranged from 40.1 percent to 51.5 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant: comfort. The outdoor relative humidity measurements ranged from 59.6 to 63.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 442 ppm to 937 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 518 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1218 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were within the NP?\AQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 3 pprn.

Respirable Particulates (PM2 §)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 29 pg/m^ with an average 20 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 99 pg/m^ to 158 pg/m^ with an average of 126 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC1OO_OO3O58762

NYC-WTC_000335303

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000335303Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292012

ATC IAQ measurements collected June 20-21, 2002 for the referenced BOE school.

Similar indexed content

Compare copies and versions →