Mr. Bernard P. Qrlan June 25, 2002 Indoor Air Quality Assessment Page 2 if^-jRULeadership^&T’ubhc^eryice(M8941 ATC Project No. 15-19125-0290
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Cunently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); nermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide io Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PA lETER iliillil Illll ORGANIZE mW
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monox ide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PVQ s) of air (ugAn^) 24-hour average 40 ug/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National F'rimary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003058761
NYC-WTC_000335302
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000335297
Indoor air quality measurements at M894; June 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292012
ATC IAQ measurements collected June 20-21, 2002 for the referenced BOE school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335293
Indoor air quality measurements at M894; June 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399500
ATC IAQ measurement letters sent to BOE regarding 90 Trinity Place, late May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399504
Correspondence about IAQ measurements at the school, May 30, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399460
ATC indoor air quality measurements report for High School for Leadership & M894 project at 90 Trinity Place, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291942
Indoor air quality measurements at HS Leadership, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260104
ATC IAQ measurements collected April 17, 2002 for HS Leadership; BOE program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397635
ATC IAQ measurements at PS 234M to evaluate indoor air conditions.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397675
ATC IAQ measurements collected to review indoor air quality status at PS 234M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397551
ATC IAQ measurements collected May 29, 2002 for PS234M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397331
Indoor air quality measurements collected April 22, 2002 at PS 234M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370524
Indoor air quality measurements collected March 20, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000335297
Indoor air quality measurements at M894; June 24, 2002.
Similar indexed content
NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
Similar indexed content
ATC IAQ measurements collected June 20-21, 2002 for the referenced BOE school.
Similar indexed content
NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
Similar indexed content
NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
Similar indexed content