Mr. Bernard P. Orlan August 28,2002
Respirable Particulate Assessment Page 2
P.S.234M ATC Project No. 15-19125-0279
Table 1 lists target guideline for the parameter that ATC evaluated during this
investigation. Meeting the listed value does not assure that acceptable indoor air quality
will be achieved at all times.
TABLE 1
TARGET GUIDELINE FOR INDOOR AIR QUALITY PARAMETER
EVALUATED
S’J
65 micrograms per cubic
Respirable meter of air (pg/m’) 24-hour USEPA NPAAQS
Particulates (PMx$) average_________________
40 micrograms per cubic USEPA recommendation for
meter of air (pg/m^) 24-hour children and sensitive
average individuals
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
RESULTS
ATC collected one (1) 24-hour gravimetric sample in the Main Lobby. The analytical
laboratory report is provided in the attachment.
The 24-hour average concentration of PM, ^ was 16.0 ug/m\ which is below both the
EPA NPAAQS for PM. 5 of 65 ug/m^ and the EPA recommended level of 40 ug/m’.