Mr. Bernard P. Orlan April 30, 2002.
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
outdoor respirable particulate concentration measurements ranged from 9 to 14 pg/m^ with an
average of 12 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO, and TVOCs were below applicable standards and guidelines.
2. All of the indoor measurements for temperature were below the range of 73 to 79^F (at 50
percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the
summer season .
3. All of the indoor measurements for relative humidity were within the ASHKAh-
recommended range of 30 to 60 percent for occupant comfort.
4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading (1202 ppm) was taken in room 510 at 9:00 AM with 28 occupants. Levels
above the recommended maximum do not indicate a health risk. Carbon dioxide
measurements are used as an indicator of available outside makeup air. The primarj' source
of CO2 indoors is occupant respiration. The school building was occupied during ATC’s
assessment.
5. All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65
pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in
aerodynamic diameter and the USEPA recommended concentration of 40, pg/m^ for
sensitive individuals and children.