IAQ report, PS 89M, Warren Street, Apr 2002

Machine-extracted title · confidence 34%

ATC IAQ measurements collected on April 29, 2002 for PS 89M.

NYC-WTC_000328318–000328322
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 30, 2002 Indoor .Air Quality Assessment Page 3 P.S.89M _________ ______________ _ ATC Project No. 15-19125-0297 Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were sur^'eyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11 ;30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 63 .9 °F to 71.1 °F. All of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 52.1 °F to 54.2 °F.

Relative Humidity

The relative humidity indoors ranged from 37.9 to 47.3 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 50.3 to 53.3 percent.

Carbun Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 496 ppm to 1202 ppm. One (1) of the indoor measurements for CO2 was above the ASEIRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 471 ppm. Therefore, the maximum acceptable level of COg at this location was 1171 ppm (background level + 700 ppm). The highest reading was taken in room 510 at 9:00 AM with 28 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of COg indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 0 ppm for all readings. These concentrations were below the .NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings. -

Respirable Particulates l^PM2 j)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 16 ug/m^. The average PM2.5 concentration for the entire school building was approximately 9 g/m^. All of the indoor and outdoor measurements were below the NPAAQS of 65 p.g/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The

CITY_21MC100_003271874

NYC-WTC_000328320

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000328320Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000199010

Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 8, 2002.

Similar indexed content

Compare copies and versions →