Mr. Bernard P. Orlan April 30, 2002
Indoor .Air Quality Assessment Page 3
P.S.89M _________ ______________ _ ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoors. All five floors of the school
building were sur^'eyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11 ;30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 63 .9 °F to 71.1 °F. All of the indoor
measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The
outdoor temperature measurements ranged from 52.1 °F to 54.2 °F.
Relative Humidity
The relative humidity indoors ranged from 37.9 to 47.3 percent. All of the indoor measurements
for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort. The outdoor relative humidity measurements ranged from 50.3 to 53.3
percent.
Carbun Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 496 ppm to 1202 ppm. One (1) of the indoor
measurements for CO2 was above the ASEIRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 471 ppm. Therefore, the maximum acceptable level of COg at this
location was 1171 ppm (background level + 700 ppm). The highest reading was taken in room
510 at 9:00 AM with 28 occupants. Levels above the recommended maximum do not indicate a
health risk. Carbon dioxide measurements are used as an indicator of available outside makeup
air. The primary source of COg indoors is occupant respiration. The school building was
occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 0 ppm for all readings. These concentrations were
below the .NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1
ppm for all collected readings. -
Respirable Particulates l^PM2 j)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 16 ug/m^. The
average PM2.5 concentration for the entire school building was approximately 9 g/m^. All of the
indoor and outdoor measurements were below the NPAAQS of 65 p.g/m3 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The