NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 24, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
* The measurements, made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
7NOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The school building was occupied at the time of the assessment.
• No smoke odor was detected in the building
• The interior of the building appeared clean and free of dust and debris.
FINDINGS ■
Based on the real-time measurements, the following findings are presented:
1.; Concentrations of COg, CO, and TVOCs were below applicable standards and guidelines.
2. All of the indoor measurements for temperature were below the range of 73 to 79°F (at 50
percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the
summer season .
3. Sixty (60) of the indoor measurements for relative humidity were below and ten (10)
measurements were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort.
4. All of the indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and
children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
A rc ASSOCIA TES INC. Reviewed by:
James R. Colm, CIH, CSP
yect Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_003271827