Mr. Bernard P. Orlan April 24,2002
Indoor Air Quality Assessment Page 3
P. S. 89M ________ _ ATC Project No. 15-19125-0297
Real-Time ENViRONMENTAi. Measlirements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy
(70) from inside the school building and ten (10) from outdoor.?. All five Boors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at
approximately 11 ;30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 64 '^F to 70.8 °F. All of the indoor
measurements for temperature were below the range of 73 to 79°F (at 50 percent relative
humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The
outdoor temperature measurements ranged from 46.8 °F to 48.1 °F.
Relative Humidity. .
The relative humidity indoors ranged fro.m 24.6 to 36.5 percent. Sixty (60) of the indoor
measurements for relative humidity were below and ten (10) measurements were within the
ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative
humidity measurements ranged from 31.8 to 34..3 percent.
Carbon Dioxide Conceiifration
Carbon dioxide concentrations indoors ranged from 472 ppm to 1050 ppm. All of the indoor
measurements for CO? were below above the ASPIRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The maximum outdoor
(background) COp concenhation .was 455 ppm. Therefore, the maximum acceptable level of
CO2 at this location was 1155 ppm (background level + 700 ppm). Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as
an indicator of available outside makeup air. The primary source of GOg indoors is occupant
respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 0 ppm for all readings. These concenfoations were
below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm
for all collected readings.
Respirahte Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 17 ug/m^. The
average PM2.5 concentration for the entire school building was approximately 9 g/m^. All of the
indoor and outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the
USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The
outdoor respirable particulate concentration measurements ranged from 16 to 20 pg/m^ with an.
average of 18 pg/m^.