Mr. Bernard P. Oflan ■ 2 March 1, 2002 Moor Air Quality Assessment Page 3 P. S. 89M 2 ATC Project No. 15-19125-0297
Real-Time ENVfRONMENTAL Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) from inside the school building and nine (9) from outdoors. AU five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:50 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 65,3°F to 72.3°F. Three (3) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the, ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 33.3 to 35.1°F.
Relative Humidity
The relative humidity indoors ranged from 11.8 to 26.8 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 31.0 to 33.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 534 ppm to 1100 ppm. All of the COp measurements were within the ASHRAE Standard 62-1999 recommended maximum concenfration of <700 ppm above the background level. The maximum outdoor (background) COp concentration was 441 ppm. Therefore^ the maximum acceptable level of GOp at this location was 1141 ppm (background level + 700 ppm). The highest GO2 measurement was collected from room 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of COp indoors is occupant respiration. The school building was occupied during ATG’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings.. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.
Respirable Particulates (PM2_3d
Respirable particulate concentrations* indoors ranged between 7 jug/m^ to 222)ug/m3, None of the measurements were above the NFAAQS of 65 jug/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMp,5 concentration for the entire school building was approximately 11 pgZm^. The PMp.5 average concentration was below the USEPA recommended concentration-'of 40 jag/m? for sensitive
CITY_21MC100_003271026
NYC-WTC_000327497
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000326923
Indoor air quality measurements at PS 89M; March 27, 2002 report.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400178
IAQ measurements report for PS 89M, March 8, 2002, ATC.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400149
IAQ measurements report for PS 89M, March 2002, ATC.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383712
IAQ measurements report for PS 89M building, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253699
IAQ data collection at PS150 M for school building air quality assessment.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202213
Letter reporting indoor air quality measurements collected at PS 89M on February 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400153
Indoor air quality measurements report for PS 89M, March 6-7, 2002, ATC.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383736
ATC IAQ measurements conducted on February 28, 2002 at PS89M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396289
ATC IAQ measurements at PS 234M, January 2002.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382671
ATC memo documenting IAQ evaluation scope at P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369306
IAQ measurements collected June 18, 2002 for BOE evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202139
ATC Associates report on indoor air quality measurements collected at P.S. 89M on March 11, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000272178
Indoor air quality measurements report for PS 234M, Feb 5, 2002.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300752
ATC reports basic IAQ parameters for PS 150M, March 2002.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000202319
Report from ATC Associates detailing indoor air quality measurements collected at a New York City Board of Education school to evaluate building conditions.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289458
ATC memo presenting indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000398145
IAQ measurements at a NYC school (P.S. 150M) for May 3, 2002, by ATC Associates.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300714
ATC IAQ measurements at PS 150M in March 2002 for pre-occupancy evaluation.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000326923
Indoor air quality measurements at PS 89M; March 27, 2002 report.
Similar indexed content
NYC-WTC_000400178
IAQ measurements report for PS 89M, March 8, 2002, ATC.
Similar indexed content
NYC-WTC_000400149
IAQ measurements report for PS 89M, March 2002, ATC.
Similar indexed content
NYC-WTC_000383712
IAQ measurements report for PS 89M building, Feb 2002.
Similar indexed content
NYC-WTC_000253699
IAQ data collection at PS150 M for school building air quality assessment.
Similar indexed content