Mr. Bernard P. Orlan March 12, 2002
Indoor .Air Quality Assessment Page 3
P. S, 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty' (30)
from inside the school building and ten (10) from outdoors. .All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began al 2:00 ?M, and concluded at
approximately 3:35 P.M.
Temperature
hidoor dry bulb temperature measurements ranged from 69.8°F to 75.6°F. One of the
measurements was above the range of 68 to 75°F (at 50 percent relative humiditx'i a.s
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 36.1 to 37.6°F.
Relative Hu miditv
The relative humidity indoors ranged from 13.6 to 17.8 percent. All of the measurements were
below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 15.8 to 18.1 percent.
Carlxin Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 486 ppm to 609 ppm. All of the COn
measurements were >vithin the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 383 ppm. Therefore, the maximum acceptable level of COn at this
location w'as 1083 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. T’he primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0
ppm for all collected readings.
Respirable Particulates (PM2,5)
P.espirable particulate concentrations* indoors ranged between 7 pg/m3 to 16 pg/m^. None of
the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMo 5
concentration for the entire school building was approximately 11 pg/m^. The PM?.5 average
concentration was below fie USEPA recommended concentration of 40 pg/ni^ for sensitive
individuals / children. The outdoor respirable particulate concentration measurements ranged
from 18 to 24 pg/m^ with an average of 21 pg/m^.