Mr. Bernard P. Grlah ■ February 7, 2002 1 n door Air Q li ality Assessment ' Page/S P. S. 89M ATC Project No. 15-19125-0297
Real-Time Envirowmjental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A.M.) and the same number of readings in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:10 A.M. and concluded after 3:30 P.M The results are described below: f
Temperatu!^
Indoor dry bulb temperature measureraents ranged from 68.4°F to 74.4°F (A.M.) and 67.9“F to 72.8°F (PM). Only one (1) measurement in the afternoon was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The average outdoor temperature was 36.0°F (A.M.) and 44.0°F (F-M.).
Relative H74mic/ity
The relative humidity indoors ranged from 12.2 to 32.0 percent (A.M.) and 13.5 to 18.8 percent (P.M.). Only two (2) readings collected in the morning were within the ASHRAE- recomniended range of 30 to 60 percent for occupant comfort. All other readings were below the recommended range. The outdoor relative humidity averaged 26.0 percent (A.M.) and 30.0 percent (P.M.). ’
CarbQnDioMde Coticentration
Carbon dioxide concentrations indoors ranged from 478 to 1004 ppm (A.M.) and 479 to 930 ppm (P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations averaged 492 ppm (A.M.) and 458 ppm (P.M.). Therefore, the maximum acceptable level of COp at this location was 1192 ppm (background level A- 700 ppm). The highest indoor level was measured in Glassroom 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COp indoors is occupant respiration. The 21'*'^ and 3 I'd floors of the school building were not occupied during ATC’s assessment.
Ca7'bonMonoxicie Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.
Respirable Particulates (PM2, 5)
Respirable particulate concentrations* indoors ranged from 11 pig/m? to 34 (A.M.) and 17 pig/m3 to 30 pig/m3 (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMp.5 concentration* for the entire school building was approximately 24 pg/ra3 (A.M.) and 23 pg/ra^ (P.M.). All A.M. and P. M. indoor measurements were also
CITY_21MC100_003270809
NYC-WTC_000327364
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000327378
Indoor air quality measurements collected February 8-11, 2002 for PS 89M.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327390
Indoor air quality measurements at a NYC school; reports reference 201 Warren Street.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327350
ATC IAQ report for the NYC Board of Education; measurements to assess air quality before occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327414
Indoor air quality measurements collected February 13, 2002 at a referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274586
LIAQ measurements at P.S. 89M to evaluate air quality before building re-occupancy, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218569
Letter reporting indoor air quality measurements collected at P.S. 89M on February 11, 2002, to evaluate conditions prior to re-occupancy.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404315
ATC IAQ measurements at PS 89M requested by NYC BOE; report with findings.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382559
Indoor air quality evaluation at P.S. 89M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404359
Indoor air quality measurements at PS 89M for re-occupancy.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382571
Indoor air quality measurements collected Feb 6, 2002 at P.S. 89M.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327374
Indoor air quality report for the NYC Board of Education at PS 89M; measurements taken mid-February.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382575
Indoor air quality measurements collected Feb 7, 2002 at P.S. 89M.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327390
Indoor air quality measurements at a NYC school; reports reference 201 Warren Street.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000327378
Indoor air quality measurements collected February 8-11, 2002 for PS 89M.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326045
Cover letter/report detailing IAQ measurements at a NYC school for BOE.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218569
Letter reporting indoor air quality measurements collected at P.S. 89M on February 11, 2002, to evaluate conditions prior to re-occupancy.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000327378
Indoor air quality measurements collected February 8-11, 2002 for PS 89M.
Similar indexed content
NYC-WTC_000327390
Indoor air quality measurements at a NYC school; reports reference 201 Warren Street.
Similar indexed content
NYC-WTC_000185979
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similar indexed content
NYC-WTC_000327350
ATC IAQ report for the NYC Board of Education; measurements to assess air quality before occupancy.
Similar indexed content
NYC-WTC_000327414
Indoor air quality measurements collected February 13, 2002 at a referenced school.
Similar indexed content