Mr. Bernard P. Grlah ■ February 7, 2002 1 n door Air Q li ality Assessment ' Page/S P. S. 89M ATC Project No. 15-19125-0297

Real-Time Envirowmjental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A.M.) and the same number of readings in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:10 A.M. and concluded after 3:30 P.M The results are described below: f

Temperatu!^

Indoor dry bulb temperature measureraents ranged from 68.4°F to 74.4°F (A.M.) and 67.9“F to 72.8°F (PM). Only one (1) measurement in the afternoon was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The average outdoor temperature was 36.0°F (A.M.) and 44.0°F (F-M.).

Relative H74mic/ity

The relative humidity indoors ranged from 12.2 to 32.0 percent (A.M.) and 13.5 to 18.8 percent (P.M.). Only two (2) readings collected in the morning were within the ASHRAE- recomniended range of 30 to 60 percent for occupant comfort. All other readings were below the recommended range. The outdoor relative humidity averaged 26.0 percent (A.M.) and 30.0 percent (P.M.). ’

CarbQnDioMde Coticentration

Carbon dioxide concentrations indoors ranged from 478 to 1004 ppm (A.M.) and 479 to 930 ppm (P.M.). All CO2 measurements collected were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations averaged 492 ppm (A.M.) and 458 ppm (P.M.). Therefore, the maximum acceptable level of COp at this location was 1192 ppm (background level A- 700 ppm). The highest indoor level was measured in Glassroom 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COp indoors is occupant respiration. The 21'*'^ and 3 I'd floors of the school building were not occupied during ATC’s assessment.

Ca7'bonMonoxicie Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2, 5)

Respirable particulate concentrations* indoors ranged from 11 pig/m? to 34 (A.M.) and 17 pig/m3 to 30 pig/m3 (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PMp.5 concentration* for the entire school building was approximately 24 pg/ra3 (A.M.) and 23 pg/ra^ (P.M.). All A.M. and P. M. indoor measurements were also

CITY_21MC100_003270809

NYC-WTC_000327364

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000327364Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, P.S.89M, 2002

NYC-WTC_000327378

Indoor air quality measurements collected February 8-11, 2002 for PS 89M.

Similar indexed content

Compare copies and versions →