Mr. Bernard P. Orlan February 5,2002 Indoor Air Quality Assessment Page 3 P. S. 89M - ATC Project No. 15-19125-0297
Real-Time Environmental Measurem ents
ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8) outdoors and thirty-two (32) inside in the morning (A.M.) and thirty-two (22) inside and eight (8) outside in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:30 P.M. The results are described below:
Temperature
Indoor dry bulb temperature measurements ranged from 66.8°F to 73.2°F (A.M.) and 67.4°F to 72.9°F (PM). Five (5) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These were readings on the 1st ,2nd and floors. The average outdoor temperature was 53.6°F (AM.) and 48.3°F (P.M.).
Relative Humidity
The relative humidity indoors ranged from 17.3 to 28.0 percent (A.M.) and 16.2 to 27.9 percent (P.M.). All readings were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity averaged 21.9 percent (A.M.) and 20.6 percent (P-M.).> ' V i
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 500 to 1109 ppm (AM.) and470 to 719 ppm (P.M.). All CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 502 ppm (A.M.) and 488 ppm (P.M.). Therefore, the maximum acceptable level of COg at this location was 1202 ppm (background level -1- 700 ppm). The highest indoor level was measured in Classroom 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 2^*1 and 3^<i floors of the school building were not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.
CITY_21MC100_003270782
NYC-WTC_000327339
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000382540
Indoor air quality measurements at P.S. 89M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400632
Report of indoor air quality measurements at PS 89M; January 28, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245428
ATC letter transmitting IAQ report and scope of work for P.S. 89M, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245442
ATC IAQ measurements report for a NYC school prior to re-occupancy, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382554
Indoor air quality measurements at P.S. 89M, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404294
IAQ measurements at P.S. 89M for re-occupancy planning.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245379
Indoor air quality measurements for BOE at P.S. 89M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326045
Cover letter/report detailing IAQ measurements at a NYC school for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373529
Indoor air quality report for P.S. 234M, January 22, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396299
ATC IAQ measurements at PS 234M, January 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000359637
ATC memo re: IAQ report for PS 89M, Warren Street.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000326825
ATC IAQ measurements at PS 89M, March 14, 2002, per BOE.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000382554
Indoor air quality measurements at P.S. 89M, Feb 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245442
ATC IAQ measurements report for a NYC school prior to re-occupancy, Feb 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382540
Indoor air quality measurements at P.S. 89M prior to re-occupancy.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245415
ATC letter transmitting IAQ report and scope of work for P.S. 89M, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400632
Report of indoor air quality measurements at PS 89M; January 28, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245379
Indoor air quality measurements for BOE at P.S. 89M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000382540
Indoor air quality measurements at P.S. 89M prior to re-occupancy.
Similar indexed content
NYC-WTC_000400632
Report of indoor air quality measurements at PS 89M; January 28, 2002.
Similar indexed content
NYC-WTC_000245428
ATC letter transmitting IAQ report and scope of work for P.S. 89M, 2002.
Similar indexed content
NYC-WTC_000245442
ATC IAQ measurements report for a NYC school prior to re-occupancy, Feb 2002.
Similar indexed content
NYC-WTC_000382554
Indoor air quality measurements at P.S. 89M, Feb 2002.
Similar indexed content