NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 89M, late March 2002

Machine-extracted title · confidence 40%

Indoor air quality measurements at PS 89M; March 27, 2002 report.

NYC-WTC_000326923–000326926
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan Indoor Air Quality Assessment Page 4 P. S. 89M ' yy A < ATC Project No. 15-19125-0297 individuals and children. The outdoor respirable particulate concentration measurements ranged from 17 to 21 pg/ni^ with an average of 19 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentrations

TVOGs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOG concentration was also 0.0 ppm. 3

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO, and TVOCs were below the applicable standards and guidelines. 2. Two (2) of the GO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 3. Sixty-nine (69) of the indoor measurements of relative humidity were below the ASHRAE recommended range of 30to 60 percent for occupant comfort. 4. All indoor temperature measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212. i i 1

Sincerely, Reviewed by: ATC ASSOCIATES INC.

Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Proj ect Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_005390566

NYC-WTC_000326926

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000326926Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →