TEM asbestos analysis, HS for Economics & Finance

Machine-extracted title · confidence 40%

TEM analysis report for HS for Economics & Finance site, Oct 4, 2001.

NYC-WTC_000324268
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 Ease 25th Street New York, New York 10010 N.Y.C. Board of Education Approved N.Y. State ELAP #1G879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/05/01 ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

ample Idencificacion Analysis Parameters

roject/Sice; H.S. for Economics % Finance. IQO Trinity Pl., NYC TEM Sample No.: 5606 60082 Entire Buildincy Dace Received: 10/04/01 Grid Openings Analysed;__ 4

Project Sample No. : HSSF-B-10./3-04 Average Grid Opening; ICS.OO um

Air Volume: 1310 liters Total Area Analyzed: 0.0450 mm2

Filter Type: MCS 25 mm diam. Pore Size: 0,45 um Analytical Sensitivity:22,;2 3/mm2 Effective Area: 385 mm2 0■0047 s/cc

FIBROUS PARTICULATES ANALYZED Jumper Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct >=5um Struct/mm2 Struct/cc nom/rnS

Chrysotile Asbestos 0 Q 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 ■ 0 0.0 0.0000

Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 0 Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 Q.Q 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED); None detected Amphibole Asbestos Type:- None detected The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method. ■

Analyzed by; Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC1OO_OO3267849 NYC-WTC_000324268

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324268Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →