AMBIENT AIR AND DUST SAMPLING PROTOCOL far PS 1 SOM Page 4 of 8

In the event that real-time measurement(s) of CO inside the school is/are greater than 5ppm and less than 9ppm, BOE will identify the source and assess the situation.

In the event that real-time measurement(s) of TVOC inside the school is/are above the cited Target Guidelines (1ppm), ATC shall immediately notify BOE representative Mr. Mohamed Hemida, the UFT and the PA consultant. BOE shall notify the school principal, the school custodian and the plant manager. The said parties will assess the situation and implement the appropriate response action(s) immediately.

In the event that real-time measurement(s) of 0.5 ppm of TVOC are obtained inside the school ATC shall immediately notify BOE representative Mr. Mohamed Hemida, the LIFT and the PA consultant. BOE shall notify the school principal, the school custodian and the plant manager. The said parties will assess the situation and implement the appropriate response action(s) immediately.

ADDITIONAL TESTING

In addition to the above, once per week, preferably on Monday, sampling settled dust for fiberglass, lead, and silica; wipe sampling for dioxin and PCB and air sampling, for heavy metals, and TVOCs shall be performed as follows;

SETTLED FIBERGLASS

• Lobby - one sample.

• Multipurpose Room near kitchen - one sample.

• Two Classrooms - 2 samples (one sample in each randomly selected classroom).

• First floor (Throughout) - Additional minimum of five (5) samples within classrooms where present. At least one sample shall be collected within every Pre-K and Kindergarten classroom where present.

Second floor Classrooms - Additional minimum of five (5) samples within classrooms where present. One sample shall be collected within every Pre-K and Kindergarten classroom where present.

• Third floor Classrooms - Additional minimum of five (5) samples within classrooms where present. One sample shall be collected within every Pre-K and Kindergarten classroom where present.

• Exterior Building Entrances - one sample on ground at the exterior of the main entrances to the school.

Dust bulk samples will be collected at the aforementioned locations and analyzed via Polarized Light Microscopy (PLM), In the event that in any of the above locations there is not sufficient amount of dust for bulk sampling and/or analysis will be noted as Not Sufficient Amount of Material for Testing (NSAMT)

CITY_21MC100_003267231

NYC-WTC_000324188

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000324188Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →