AMBIENT AIR AND DUST SAMPLING PROTOCOL for PS/IS89M. Page 4 of 8
In the event that real-time measurement(s) of CO inside the school is/are greater than 5ppm
and less than 9ppm, BOE will identify the source and assess the situation.
In the eventthat real-time measurement(s) of TVOC inside the school is/are above the cited
Target Guidelines (1 ppm), BOE will immediately notify the UFT. the school principal, the
school custodian and the PA consultant. The said parties will assess the situation and
implement the appropriate response action(s).
In the event that real-time measurement(s) of 0.5 ppm of TVOC are obtained inside the
school BOE will notify the UFT, the school principal, the school custodian and the PA
consultant. The said parties will assess the situation and implement the appropriate response
action(s)
ADDITIONAL TESTING
In addition to the above, once per week, preferably on Thursday, sampling settled dust for
fiberglass, lead, and silica; wipe sampling for dioxin and PCB and air sampling, for heavy
metals, and TVOCs shall be performed as follows:
SETTLEDHBERGLASS
• First floor hallway outside cafeteria - 2 samples.
• Cafeteria - one sample.
• Gymnasium - one sample.
• Auditorium - one sample.
• Classroom with north side unit ventilators - one sample immediately after the last class.
• Classroom with east side unit ventilators - one sample immediately after the last class.
• Classroom with south side unit ventilators - one sample immediately after the last class.
• Second floor Hallways south end - one samples immediately after the last class.
• Fourth floor Hallways south end - one samples immediately after the last class.
Dust bulk samples will be collected at the aforementioned locations and analyzed via
Polarized Light Microscopy (PLM). In the eventthat in any of the above locations there is not
sufficient amount of dust for bulk sampling and/or analysis will be noted as Not Sufficient
Amount of Material for Testing (NSAMT)
In the event that any of PLM analysis detect more than 1% by weight of fiberglass, BOE will
immediately notify the UFT, the school principal, the school custodian and the PA consultant.
The said parties will assess the situation and implement the appropriate response action(s).
LEAD SURFACE DUST
NYC-WTC_000236850