Mr. Bernard P. Orlan November 16, 2001 . Indoor .Air Qualily Assessment Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
R E A L-TIM EEWI RON M ENTAL MEASI i R E M ENIS
ATC collected one hundred and sixty-two (162) sets of real-time environmental measurements consisting of one hundred and sixty (160) in the school building and two (2) outdoors. All seven Poors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8;30 P..M. and concluded after 4:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.4 °F to 78.5 °F. Eighty-three (83) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 35-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 60.4 and 76.2 °F.
Re/iiiive Humiditv
The relative humidity indoors ranged from 41.2 percent to 46.8 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 43.2 to 52.8 percent.
Carban Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 539 ppm to 1116 ppm. All COo measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 428 and 460 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1160 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-1 ppm.
Respirable Tariiculaies (PMp SJ
Respirable particulate concentrations* indoors ranged between 60 pg/m^ to 120 pg/m^ with an average of approximately 77 gg/m^. Only seven (7) measurements were below the NPAAQS of 65 Lig/mJ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 124 and 148 pg.'mJ.
* The measurements made during this assessment were instantaneous readings, the guidelines are adopted from 24-hour and annual averages.
CITY_21MC1OO_OO3266844
NYC-WTC_000323927
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
11 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
11 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
9 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292982
IAQ assessment conducted at Stuyvesant High School on Oct 23, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336113
May 2002 IAQ measurements at Stuyvesant High School per BOE request.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
Similar indexed content
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similar indexed content
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content