Mr. Bernard P, Orian November 16, 2001 Indoor Air Quality Assessment Page 2 Stuyvesant Hiuh School (M477~) ATC Project No. 15-19125-0246
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of lime, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Veniilation for Accepiabfe Indoor Air Ovciliiy (ASHRAE 62-}999j, American Society of Heating. Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmenicil Conclilionsjdr Human Occupancy (ASHRAE 55-J992}: Indic'ii.ricil Hy^^ienixix Guide lo Indoor Air Oiialiry Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO?) above background level Carbon Monoxide 9 ppm USEPA NPAAQS (as cited in (CO) ASHRAE 62) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM?.5) of air (pg/mJ) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE55 Winter: 68-75°Fat5O% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile I ppm Organic Compounds Al HA (TVOC) LSEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003266843
NYC-WTC_000323926
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
11 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
11 shared non-person entities · 1 shared topics · similarity 0.990
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
9 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292901
IAQ field report correspondence for Stuyvesant H.S. dated Oct 17, 2001.
9 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.989
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323919
ATC Associates indoor air quality assessment at a NYC school in mid-November 2001.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
Similar indexed content
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similar indexed content
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content