Mr. Bernard P. Orkin November 15.2001 • Indoor Air Oualily Assessment Page 3 .Sluwesant High Sc hoot (M477) ATC Project No. 15-19125-0246
REAL-TIME EN\ IRONMEATAL MEASfREMENTS
ATC collected sixty (60) sets of real-time environmental measurements consisting of (59) in the school building and one (1) outdoors. All seven lloors of the school were surveyed. These results arc described below. Field data sheet.s are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 3:00 P.M.
Teiiiperaliire
Indoor dry bulb temperature measurements ranged from 73.1 °F to 77.6 °F. Forty-four (44) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature was 67.5 °F.
Rc/cilive Himudilv
The relative humidity indoors ranged from 30.3 percent to 37.6 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 39.9 percent.
C'cirhon Dioxid^oncenlrarion
Carbon dioxide concentrations indoors ranged from 534 ppm to 980 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COn concentration was 486 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1 1 86 ppm (background level - 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Ccirhtm Monuxit/e Concenmiiion
Carbon monoxide concentrations indoors were 1 ppm for ail readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1-2 ppm.
Respirable Pciriicti/ciles (PM?
Respirable particulate concentrations* indoors ranged between 42 Ltg/mo to 100 pg/m^ with an average of approximately 83 pg/m^. Only five (5) measurements were below the NPAAQS of 65 pg/m- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentratioms were 103 pg/np.
* I he measurements made during this assessment were instantaneous readings, the guidelines are aiiopted from 24-110111-and annual averages.
CITY_21MC1OO_OO3266832
NYC-WTC_000323921
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
11 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311783
ATC IAQ assessment conducted at Stuyvesant High School for NYC BOE.
11 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.988
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311814
ATC letter transmitting IAQ assessment results for Stuyvesant HS.
10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271154
UAQ indoor air quality assessment report for Stuyvesant High School in Oct 2001.
11 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312060
ATC IAQ assessment conducted at Stuyvesant High School on November 14, 2001.
11 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197518
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in October 2001.
10 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000323931
ATC Associates is pleased to provide this report of an indoor air quality assessment.
11 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000197564
Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000197574
Letter from ATC Associates reporting indoor air quality measurements collected at a Board of Education school in November 2001.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253707
IAQ measurements collected at PS 150 M, including TVOCs and humidity.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311998
Nov 8, 2001 memo re: IAQ assessment at Stuyvesant High School (M477).
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253623
ATC IAQ measurements conducted for BOE pre-occupancy evaluation.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000323925
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000323939
ATC Associates IAQ assessment report for the school in New York City.
Similar indexed content
NYC-WTC_000323908
ATC Associates indoor air quality assessment at a New York City school on Nov 15, 2001.
Similar indexed content
NYC-WTC_000323914
ATC Associates indoor air quality assessment at a NYC school on Nov 16, 2001.
Similar indexed content
NYC-WTC_000271149
Indoor air quality assessment conducted on Oct 18, 2001 at Stuyvesant HS.
Similar indexed content