104 Easl 25th St New York, New York 1001O www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.

Mr. Bernard P. Orlan June 6,2002 Page 2

2. IS 306X

A total of ten (10) dust wipe samples were collected from selected unit ventilators throughout the school. Laboratory analysis detected lead concentrations which ranged between 1,817.0 pg/ft^ to 259.4 pg/ft^. The average concentration was 806.38 pg/ft^.

B. LEAD WIPE SAMPLING -HVAC UNITS

1. STUYVESANT HIGH SCHOOL

A total of fifteen (15) dust wipe samples were collected from various HVAC units throughout the school. Laboratory analysis detected lead concentrations which ranged between 253.0 pg/ft^ to less than the limit of detection of 9.0 pg/ft^. The average concentration was 89.16 pg/ft".

2. IS 306X

A total of eighteen (18) dust wipe samples were collected from various HVAC units throughout the school. Laboratory analysis detected lead concentrations which ranged between 466.7 pg/ft^ to 18.5 pg/ft^. The average concentration was 159.45 pg/ft^.

Exact sample locations and analytical laboratory results for the samples collected at each school is included in Appendix A of this report.

C. DIOXIN BULK SAMPLING - STUYVESANT HIGH SCHOOL

ATC collected twenty-four (24) samples for PCDDs/PCDFs (plus two blanks) within Unit Ventilators and HVAC units at Stuyvesant High School. All samples were submitted for laboratory analysis to Pace Analytical Services, Inc. (Pace) of Minneapolis, MN, a laboratory experienced in dioxin analysis. The analysis was performed by modified EPA Method 8290 using combined capillary column gas chromatography/high resolution mass spectrometry.

Each sample was analyzed for sixteen (16) PCDD/PCDF isomers. The results for each isomer were then converted to 2, 3, 7, 8 tetrachloro-dibenzo-p-dioxin (2, 3, 7, 8-TCDD) equivalents by multiplying by an established equivalency factor. This provides a single value for the analytical results for each sample.

CITY_21MC100_000948502 NYC-WTC_000321493

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000321493Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →