NYC 9/11 Public Portal Document
104 East 25lh St., 10th Ff
New York, New York 10010
www.atc-enviro.com
212353 8280
Fax 212 353.8305
ASSOCIATES INC.
August 30, 2002
Mr. Bernard P. Orlan
Director, Environmental Health and Safety
New York City Department of Education
28-11 Queens Plaza North
Long Island City, NY 11101
Re: Air Sampling for Mercury Vapor
Dr. Sun Yat Sen School (I.S. 131M)
ATC Project No. 15-19125-0346
Dear Mr. Orlan:
ATC Associates, Inc. (ATC) is pleased to provide this report of the results of air sampling for
mercury vapor conducted on August 22, 2002, at the referenced school. The New York City
Department of Education (DOE) requested this sampling prior to the resumption of classes to
verify that acceptable indoor air quality is being maintained.
Scope of Work
ATC collected three (3) samples for mercury vapor using Carulite® (Hydrar) tubes connected to
battery-powered sampling pumps calibrated to collect 0.2 liters of air per minute. Samples were
collected for ten (10) hours. Two (2) samples were collected outdoors and one (1) was collected
indoors. The samples were sent to PSC Analytical Services, Inc., an American Industrial Hygiene
Association-accredited laboratory in Reading, PA. One blank tube w^as also submitted. Analysis
was performed by mea is of a mercury analyzer according to NIOSH Method 6009. A copy of
the analytical laborator ' report is attached.
Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists from ATC’s New York City
office, collected the samples consistent with accepted industrial hygiene sampling practices. The
results represent the conditions on the day the samples were collected.
The sampling locations were; the L‘ floor Main Lobby, 2"^* Floor Hallway by Room 210 and 3^**
Floor Hallway by Room 327.
Results
Mercury was detected in these samples at levels that were indistinguishable from those detected
in the blanks.
The established regulatory value for mercury (O.lmg/m’) is intended for industrial workplace
exposures and is not generally applicable to office/school settings. There are no standards for
mercury in indoor air n non-industrial situations. The EPA has no standard or guideline for
mercury vapor in ambient air.
CITY_21MC100_003048787
NYC-WTC_000316269
OCR can misread numbers and units. Confirm readings against the page image before using them.