Mr. Bernard P. Orlan June 25, 2002 Indoor Air Quality Assessment Pages P. S. 234M ArCPrpiectNpJ521912S0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 07:00 AM and concluded after 12:50 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 73.1 °F to 76.1 °F. All of the indoor measurements for temperature were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature measurements were 76.9 and 77.9 °F.

Relative Humidity

The relative humidity indoors ranged from 48.1 percent to 58.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE-reconunended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 52.9 and 55.3 percent.

CarbonDipxide Concentration

Carbon dioxide concentrations indoors ranged from 570 ppm to 1235 ppm. All of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 616 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1316 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.

Respirable Particulates (PM2_§)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 49 pg/m^ with an average approximately 27 pg/m^- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eight (8) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_003032784

NYC-WTC_000315469

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000315469Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →