Mr. Bernard P. Orlan June 21,2002 Indoor Air Quality Assessment Pages P. S. 234M ATC Project No. 15-19125-0279 1
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7; 00 AM and concluded after 12:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.9 °F to 76.1 °F. Twenty-one (21) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 69.9 and 76.1 °F.
Relative Humidity
The relative humidity indoors ranged from 48.9 percent to 57.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 63.5 and 63.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 510 ppm to 1347 ppm. All of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 710 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1410 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CgrbpnMpnwddeCpnceritratipn
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.
Respirable Particulates (PM2_§)
Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 47 pg/m^ with an average approximately 22 pg/m^- None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive
CITY_21MC100_003032762
NYC-WTC_000315447
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000397705
ATC IAQ measurements report for PS 234M; scope of work noted.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372193
SCOPE OF WORK for indoor air quality testing at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397719
ATC indoor air quality measurements reported for PS 234M; June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372213
ATC IAQ measurements at PS 234M, June 24, 2002, BOE-requested.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315467
ATC IAQ measurements report for BOE at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397301
IAQ measurements collected April 17, 2002 at PS 234M for BOE evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371847
Indoor air quality measurements report for PS 234M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397685
ATC report of lAQ measurements conducted on June 18, 2002 for PS 234M as part of BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315456
ATC report of IAQ measurements at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397715
ATC report on IAQ measurements at PS 234M for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372173
SCOPE OF WORK for IAQ tests at PS 234M, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372203
ATC report detailing IAQ measurements at PS 234M, June 21, 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397705
ATC IAQ measurements report for PS 234M; scope of work noted.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397695
ATC IAQ measurements report for PS 234M; measures for BOE monitoring program.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372193
SCOPE OF WORK for indoor air quality testing at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315482
ATC IAQ measurements at PS 234M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397675
ATC IAQ measurements collected to review indoor air quality status at PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397715
ATC report on IAQ measurements at PS 234M for BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000397705
ATC IAQ measurements report for PS 234M; scope of work noted.
Similar indexed content
NYC-WTC_000372193
SCOPE OF WORK for indoor air quality testing at PS 234M.
Similar indexed content
NYC-WTC_000397719
ATC indoor air quality measurements reported for PS 234M; June 2002.
Similar indexed content
NYC-WTC_000372213
ATC IAQ measurements at PS 234M, June 24, 2002, BOE-requested.
Similar indexed content
NYC-WTC_000315467
ATC IAQ measurements report for BOE at PS 234M.
Similar indexed content