Mr. Bernard P. Orlan March 5, 2002 Indoor Air Quality Assessment Page 2 P, S. 234M ATC Proiect No. 15-19125-0279 •
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. Tire information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatoi-y standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-J999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 66-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GI IDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER TARGET LEVEL iitl AGENCY OR SbBIk lllllll ■IIIIIIO ‘Sffgv’ ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2)_____________ above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (p,g/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - recommendation for children/sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75’F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_003032154
NYC-WTC_000314915
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199221
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 6, 2002 for the NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000377084
Correspondence reporting indoor air quality measurements at a NYC school.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000215155
Report summarizing indoor air quality measurements collected at a high school location in February 2002 to assess environmental conditions.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314924
ATC IAQ measurements collected at P.S. 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315332
ATC letter accompanying IAQ measurements report for P.S. 234M, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000182879
Report of indoor air quality measurements collected at PS 234M on February 11, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382635
ATC IAQ measurements at P.S. 89M to evaluate school air quality.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328284
ATC IAQ measurements completed for NYC BOE at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381390
Indoor air quality measurements collected at PS 234M; March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000218435
ATC Associates submitted an indoor air quality measurement report for P.S. 234M collected on February 1, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000360262
ATC memo transmitting IAQ measurements for PS 89M dated March 4, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
Similar indexed content
NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
Similar indexed content
NYC-WTC_000376915
IAQ measurements report for M894 site at Trinity Place, BOE request.
Similar indexed content
NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
Similar indexed content