Mr. Bernard P. Orlan February 27, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50)
from inside the school building and ten (10) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after
3:45 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.9 °F to 76.0 °F. Six (6)
measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature measurements ranged from 55.0 to 56.5 °F.
Relative Humidity
The relative humidity indoors ranged from 31.0 percent to 39.6 percent. All of the measurements
were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The
outdoor relative humidity ranged from 38.6 to 40.0 percent.
CarbonDioxideConcentration
Carbon dioxide concentrations indoors ranged from 570 ppm to 1303 ppm. Nine (9) of the
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the backgroimd level. The maximum outdoor (background)
CO2 concentration was 520 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1220 ppm (backgroimd level + 700 ppm). The highest measurement was recorded
in room 215. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source of
CO2 indoors .is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were
also 0 ppm.
Respirable Particulates
Respirable particulate concentrations* indoors ranged between 17 pg/m^ to 34 pg/m^. All
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 26 pg/m^. This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
25 to 36 pg/m^ with an average of 30 pg/m^.