Mr. Bernard P. Orlan March 7, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279 Real-Time environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded after 1:55 P,M,
Temperature
Indoor dry bulb temperature measurements ranged from 70.2 °F to 78.0 °F. Eighteen (18) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 37.3 to 44.3 °F.
Relative Humidity
Ure relative humidity indoors ranged from 17.0 percent to 21.0 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 24.0 to 27.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 609 ppm to 907 ppm. All of the measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 520 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1220 ppm (background level -E 700 ppm). The highest measurement was recorded in room 302. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
CarbonMonoxideConcentrajion
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 22 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2,5 concentration for the entire school building was approximately 17 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 19 to 30 pg/m3 with an average of 21 pg/m^.
CITY_21MC100_003083605
NYC-WTC_000294379
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000382080
ATC Associates indoor air quality report for PS 234M dated February 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382090
Report of indoor air quality measurements at a New York City school, requested by the Board of Education, Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314934
Indoors air quality measurements at P.S. 234M per BOE request.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314656
ATC report detailing IAQ measurements at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
12 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199183
Letter from ATC Associates reporting indoor air quality measurements collected at P.S. 234M on March 6, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314670
ATC indoor air quality measurements report for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314904
ATC IAQ report for P.S. 234M detailing measurements and BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314865
IAQ measurements collected March 12, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314835
IAQ measurements collected March 15, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314666
IAQ measurements report for PS 234M (Feb 2002).
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314855
IAQ measurements collected March 13, 2002 at PS 234M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000382090
Report of indoor air quality measurements at a New York City school, requested by the Board of Education, Feb 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382080
ATC Associates indoor air quality report for PS 234M dated February 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314670
ATC indoor air quality measurements report for PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314924
ATC IAQ measurements collected at P.S. 234M for BOE.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000382080
ATC Associates indoor air quality report for PS 234M dated February 2002.
Similar indexed content
NYC-WTC_000382090
Report of indoor air quality measurements at a New York City school, requested by the Board of Education, Feb 2002.
Similar indexed content
NYC-WTC_000314934
Indoors air quality measurements at P.S. 234M per BOE request.
Similar indexed content
NYC-WTC_000314656
ATC report detailing IAQ measurements at PS 234M.
Similar indexed content
NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
Similar indexed content