NYC 9/11 Public Portal Document
ATC Associates
. 104 East 25 Street, New York, NY 10010
Phone: (212)353-8280 Fax:(212)353-8306
Attn: Mr. Bernard Orlan Received: 1/28/02 9:00:00 PM
N.Y.C. Board of Education
28-11 Queens Plaza North ATC Group#: 6492
Long Island City, NY 11101 Analysis Date: 1/28/02
Fax: (212) 475-4122 Phone:' (212)477-8941
Project: PS 89M 201 Warren Street, New York, NY
Playground, Roof ,1st Floor Hallway
Asbestos Fiber Analysis by Transmission Electron Microscopy (TEM) Performed
by EPA 40 CFR Part 763 Final Rule (AHERA)
Analytical Asbestos
Area Nan Asbestos Structures Sensitivity Concentration
Sample Volume Analyzed Asb 0.5fi-S 5fi (S/cc) (S/mm^) (S/cc) Notes
01 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -1
02 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -2
03 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -3
04 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492-4
05 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -5
06. 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -6
07 1840.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6492 -7
08 1840.00 0.0450 0 None Detected 0 0 0.0047 <22,24 <0.0047
6492 -8
MARK PEYSAKHOV MICHAEL A, GORYCKI, Ph.D.
Analyzed by: Approved by:
Disciaimer The laboratory is not responsible for data reported in structures/oc, which is dependent on volume collected by non-laboratory personnel. This lab Is only responsible
for data reported In structures/mmL This report may not be reproduced, except in full, without written approval by ATC Associates Inc. This report may not be used to claim
product endorsement by NVLAP or any other agency of the U.S. Government This reports relates only to the samples reported above. Quality control data (including 95%
confidence limits and laboratory and analysis' accuracy and precision) is available upon request
Accredited for NVLAP PLM/TEM #101187-0, NY State ELAP #10879
CITY_21MC100_0 03047196
NYC-WTC_000312945