Mr. Bernard P. Orlan March 1, 2002
Air Sampling for Metals Page 2
Stuyvesant High School ATC Project No. 15-19125-0246
RESULTS
Chromium was detected in all of the samples obtained (including the blank). Blank-correcting
the samples will lower the chromium concentrations to below the limit of detection of the
analytical method.
The Environmental Protection Agency (EPA) has set a screening level for hexavalent chromium
in air of 0.6 ug/m\ this assumes a continuous exposure for one year. The samples here were
analyzed for total chromium (trivalent and hexavalent). Blank-corrected chromium concentrations
are well below the EPA level.
Copper was detected at 0.295 micrograms, which is slightly above the analytical limit of
detection of 0.2 micrograms in the sample collected at the 2”“^ floor bridge entrance hallway
(Sample #ATC-0213-STUY-M2). The resulting calculated airborne concentration at the location
was 0.308 micrograms per cubic meter of air. Copper was not detected in the blank above the
analytical limit of detection.' The EPA has not established a screening limit or guideline for
copper.
No other metals were detected in the samples above the limit of detection for the analytical
method.
ATC appreciates the opportunity to provide this indoor air quality service to the BOE. Please call
me at (212) 353-8280 extension 212 if you have any questions.