Mr. Bernard P. Orlan November 2. 2001 Indoor Air Quality .Assessment Page 3 Stuvvesant High School (M477) ATC ProjectNo. 15-19125-0246

Real-Time Enx^ronmental Measurements

ATC collected one hundred and fifteen (115) sets of real-time environmental measurements consisting of one hundred and thirteen (113) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheers are found in Attachment I. Readings began at 9:00 A.M. and concluded after 2;20 P.M.

Tempercitiire

Indoor dry bulb temperature measurements ranged from 72.2 °F to 79.3 Seventy-two (72) measurements were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on all floors. The outdoor temperature range was 61.9to 71.8 °F.

Relative Humidity

The relative humidity indoors ranged from 36.9 percent to 50.2 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 38.7 to 44.2 percent.

Car^n Dioxide Coticentra/ion

Carbon dioxide concentrations indoors ranged from 438 ppm to 1850 ppm. Eleven (II) COo measurements were above the ASHRAE Standard 62-1999 recommended maxi mum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations were 395 and 400 ppm. Therefore, the maximum acceptable level of COg at this location was 1100 ppm (background level -i- 700 ppm). The highest reading, 1850 ppm, was in Room 303. Rooms with CO? levels above the recommended maximum were found on the 2nd, 3''‘^, 4^h, 5^1'', 7th and floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COg indoors is occupant respiration.

Carbon Monoxide CpncenDigtion

Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM?

Respirable particulate concentrations indoors ranged between 37 gg/m^ and 88 pg/mA Eighteen (18) of the measurements were above the NPAAQS of 65 ug/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 83 and 107 pg/m^.

CITY_21MC100_0 03045778

NYC-WTC_000311924

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311924Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, November 2001

NYC-WTC_000197564

Letter from ATC Associates reporting an indoor air quality assessment conducted at a Board of Education school in November 2001.

Similar indexed content

Compare copies and versions →