NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan October 26, 2001
Indoor Air Quality Assessment Page 4
Stuwesant Hiah School fM477) ATC Project No. 15-19125-0246
7V0C Concentration
TVOC concentrations indoors were 0.0 ppm for al] readings. These concentrations were below
the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration
was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• All windows were closed except for windows in Room 931 and Room 1004;
• No smoke odor was detected in the building;
FINDINGS
Based on the visual inspection of the occupied spaces and real-time measurements, the following
findings are presented;
1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards
and guidelines.
2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All
others were below the recommended maximum concentration.
3. Five (5) temperature measurements were above the range recommended by ASHRAE 62-
1999.
4. One (1) relative humidity measurement was marginally above the range recommended by
ASHRAE 55-1992.
CONCLUSION
Based on our observations and measurements, ATC concludes that the assessed locations were
suitable for occupancy at the time of ATC’s investigation. Some individuals may find the
conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for
increased outdoor air.
CITY_21MC100_003045693
NYC-WTC_000311849