Mr. Bernard P. Orlan October 26, 2001 Indoor Air Quality Assessment Page 4 Stuwesant Hiah School fM477) ATC Project No. 15-19125-0246

7V0C Concentration

TVOC concentrations indoors were 0.0 ppm for al] readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • All windows were closed except for windows in Room 931 and Room 1004; • No smoke odor was detected in the building;

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented;

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Twelve CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Five (5) temperature measurements were above the range recommended by ASHRAE 62- 1999.

4. One (1) relative humidity measurement was marginally above the range recommended by ASHRAE 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the conditions in some rooms to be uncomfortable. The elevated CO2 levels indicate the need for increased outdoor air.

CITY_21MC100_003045693

NYC-WTC_000311849

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311849Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000271198

Indoor air quality assessment report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →