October 26, 2001
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment
Stuyvesant High School (M477)
345 Chambers Street
New York, New York 10007
ATC Project No. 15-19125-0246
Dear Mr. Orlan;
ATC Associates Inc. (ATC) is pleased to provide this report of an indoor air quality (lAQ)
assessment conducted on October 25, 2001, at the referenced school. The New York City Board
of Education (NYC-BOE) requested this assessment to determine if acceptable indoor air quality
is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to asse.ss the basic parameters of temperature, relative humidity,
carbon dioxide (CO;) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Tenzin Namgyal and Wagdi Abdelshahid, Industrial Hygienists, of ATC’s New York City office,
conducted the assessment. ATC’s findings and conclusions are based on a visual inspection,
real-time environmental measurements and conditions present in the school at the time of the
assessment.
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates with a Dust-Trak® Aerosol Monitor
Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a R.AE Systems, Inc. MiniR.\E® photoionization
detector (PID).