NYC 9/11 Public Portal Document

Mr. Bernard P, Orlan October 16. 2001 Indoor Air Quality Assessment Page 4 Stuwesant H.S. fM477') ATC Project No. 15-19125-0246

TJ'OC Concentration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AIHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • All the windows in the building were closed, except for windows in Rooms 303, 717 & dining room; • There was a paint odor in art classroom 1006; • The teacher in Room 726 was told by ATC representatives to move the books blocking the Univent cover; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment.

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Concentrations of CO, TVOCs and respirable particulates were within applicable standards and guidelines.

2. Fourteen CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Two temperature measurements, in Rooms 222 and 225, were above the range recommended by ASHRAE 55-1992.

4. One measurement of relative humidity, in Room 1006, was above the range recommended by ASHRAE 55-1992.

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATC’s investigation. Some individuals may find the temperature in some rooms to be uncomfortable.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep CO2 levels and temperatures within established guidelines by using adequate ventilation; • Dissipate odors through increased natural/mechanical ventilation;

CITY_21MC100_003045554

NYC-WTC_000311751

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311751Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292885

IAQ field report for Stuyvesant High School dated Oct 16, 2001.

Similar indexed content

Compare copies and versions →