Mr. Bernard P. Orlan October 15, 2001 Indoor Air Quality Assessment Page 4 Stuvvesant H.S. fM477) ATC Project No. 15-19125-0246

TVOC Concentration

TVOC concentrations indoors were 0.0 ppm for all readings. These concentrations were below the AJHA guideline of 1 ppm for non-industrial buildings. The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • Windows in few classrooms were open. Teachers were told to keep the windows closed; • The interior of the building appeared clean and fi-ee of dust and debris; • The building was occupied at the time of the assessment; • A smoke odor was detected in the main entrance lobby. The same odor was detected outdoors.

FINDINGS

Based on the visual inspection of the occupied spaces and real-time measurements, the following findings are presented:

1. Measurements of temperature and concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Ten CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. One (1) relative humidity measurement, collected in Room #303, was above the range recommended by ASHRAE 55-1992.

4. Respirable particulates concentrations were below the NPAAQS/ASHRAE guideline of 50 pg/m3 except the reading taken in Room #337 which was 50 pg/m^

CONCLUSION

Based on our observations and measurements, ATC concludes that the assessed locations were suitable for occupancy at the time of ATG’s investigation. Some individuals may find the temperature in some rooms to be uncomfortable.

RECOMMENDATIONS

Based on the findings and conclusions above, ATC recommends the following:

• Keep CO2 levels and temperatures within established guidelines by using adequate ventilation; • Dissipate odors through increased natural/mechanical ventilation; • Conduct timely follow-up monitoring/inspection to ensure that recommendations were effective.

CITY_21MC100_006797341

NYC-WTC_000292883

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000292883Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292885

IAQ field report for Stuyvesant High School dated Oct 16, 2001.

Similar indexed content

Compare copies and versions →