Mr. Bernard P. Orlan October 15, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant H.S. (M477) ATC Project No. 15-19125-0246

SAMPLmGRESULTS

Real-Time Enxtronmental Measurements

ATC collected ninety-nine (99) sets of real-time environmental measurements consisting of ninety-eight (98) in the school building and one (1) outdoors. These results are described below. Field data sheets are found in Attachment 1.

Temperature

Indoor dry bulb temperature measurements ranged from 69.6 °F to 75.9 °F. All collected measurements were within the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season ('wintertime conditions). The outdoor temperature was 75.1°F.

Jielative Humidity

The relative humidity indoors ranged from 50.4 percent to 61.0 percent. The 61.0% level was in Room 303, all other measurements were within ASHRAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 50.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 494 ppm to 1899 ppm. Ten (10) CO2 measurements were at or above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the backgroimd level. The outdoor (background) CO2 concentration was 397 ppm. Therefore, the acceptable level of CO2 at this location was 1097 ppm (background level + 700 ppm). Rooms with high CO2 levels were found on all floors except the pt, 5th and 9^ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates

Respirable particulate concentrations indoors ranged berwesn 18 pg/m^ and 50 pg/m^. Only the reading collected in Room #337 was equal to the NPAAQS/ASHRAE guideline of 50 pg/m^ (annual average concentration of particulate matter 10 micrometers or less in aerodynamic diameter). The outdoor respirable particulate concentration range was 58 pg/m^.

CITY_21MC100_003045537

NYC-WTC_000311734

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311734Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000292885

IAQ field report for Stuyvesant High School dated Oct 16, 2001.

Similar indexed content

NYC-WTC_000292854

IAQ assessment report for Stuyvesant High School, dated Oct 11, 2001.

Similar indexed content

Compare copies and versions →